Forney Corporation
Igniter Configurator
NFPA 85 sizing · instant budgetary quote
WINDBOXFURNACEMAIN BURNER 180 MMBTU/HRHESI 12 JGAS INLET · FLEX HOSEAIR 80 SCFMINTEGRAL DET.4" OD24" INSERTION18 MMBtu/hrCLASS 1 · 10.0% OF MAINBURNER FRONT · 8 IGNITERSFORNEY MAXFIRE 140RANGE 525 MMBTU/HR · TUBE 4"FUEL PRESS 1525 PSIG · SECTION A-A
NFPA 85 Class 1 sizing (≥ 10% of main burner)
18 MMBtu/hr target · 10% of 180 MMBtu/hr
MAXFire® 140 capacity envelope
5–25 MMBtu/hr
Fuel supply pressure
20 psig available · 15–25 psig required
Cooling & combustion air
80 scfm @ 6" w.c. above windbox
Verify available fan margin at commissioning.